thegladiator كبير مهندسين
عدد المساهمات : 783 تاريخ التسجيل : 02/02/2008 العمر : 37 رقم العضوية : 547 Upload Photos :
| موضوع: DIFFERENTIAL PROTECTION الأحد 1 يونيو - 15:14 | |
| DIFFERENTIAL PROTECTION Differential protection is a very reliable method of protecting generators, transformers, buses, and transmission lines from the effects of internal faults.
In a differential protection scheme in the above figure, currents on both sides of the equipment are compared. The figure shows the connection only for one phase, but a similar connection is usually used in each phase of the protected equipment. Under normal conditions, or for a fault outside of the protected zone, current I1 is equal to current I2 . Therefore the currents in the current transformers secondaries are also equal, i.e. i1 = i2 and no current flows through the current relay. If a fault develops inside of the protected zone, currents I1 and I2 are no longer equal, therefore i1 and i2 are not equal and there is a current flowing through the current relay.
Differential Protection of a Station Bus The principle of the differential protection of a station bus is the same as for generators. The sum of all currents entering and leaving the bus must be equal to zero under normal conditions or if the fault is outside of the protected zone. If there is a fault on the bus, there will be a net flow of current to the bus and the differential relay will operate. Percentage Differential Relays The disadvantage of the current differential protection is that current transformers must be identical, otherwise there will be current flowing through the current relays for faults outside of the protected zone or even under normal conditions. Sensitivity to the differential current due to the current transformer errors is reduced by percentage differential relays. [size=16]In percentage differential relays, the current from each current transformer flows through a restraint coil. The purpose of the restraint coil is to prevent undesired relay operation due to current transformer errors. The operating coil current | i1 - i2 | required for tripping is a percentage of the average current through the restraint coils. It is given by where k is the proportion of the operating coil current to the restraint coil current. For example if k = 0.1, the operating coil current must be more than 10% of the average restraint coil current in order for the relay to operate.
| |
|
الزعيــم كبير مهندسين
عدد المساهمات : 678 تاريخ التسجيل : 01/05/2008 العمر : 42 الموقع : أمة المصطفى رقم العضوية : 1098 Upload Photos :
| موضوع: رد: DIFFERENTIAL PROTECTION الأحد 1 يونيو - 15:37 | |
| شكرا على هذا الموضوع الممتاز ولكن توجد ملاحظة بسيطة بعض الشركات المصنعة للمولدات تقوم بقفل نقطة الstar point ....وهذا اكبر خطأ ويجب عليك كمهندس مسئول رفض استلام المولد لاحظ ان الست اطراف الناتجة عن لف المولد ماهى الا ثلاث بدايات وثلاث نهايات الخرج 3 فاز كل فاز بداية ونهاية ... المجموع = 6 اطراف ومن ثم عندما تضع محولات التيار على الثلاث بدايات وتضع محولات التيار على الثلاث نهايات تكون عملت وقاية على المولد وهذه الحماية ياجماعة مهمة جدا جدا جدا جدا بل اهم حماية على المولد اما بالنسبة للمذكور اعلاه بخصوص ان هذه الحماية حساسة جدا لاى تغيير فى التيار جميع اجهزة الوقاية المستخدمة فى السوق حاليا تتيح لك تغيير القيم لما تراه انت مناسبا وانت اللى هتشيل ياريس
| |
|
thegladiator كبير مهندسين
عدد المساهمات : 783 تاريخ التسجيل : 02/02/2008 العمر : 37 رقم العضوية : 547 Upload Photos :
| |
الزعيــم كبير مهندسين
عدد المساهمات : 678 تاريخ التسجيل : 01/05/2008 العمر : 42 الموقع : أمة المصطفى رقم العضوية : 1098 Upload Photos :
| |